Programmable universal HVAC controller, Excel 800
 |
| EXCEL 5000 DDC controller for all HVAC control applications, and building automation
functionalities. The controller can be applied
for stand-alone operation, dial-up and in network systems. |
| For all buildings. |
|
| Control software |
| • |
free programmable with CARE software |
| • |
programmable with standard ModAL software modules |
|
| Hardware inputs |
Panel Bus and LON Bus input modules available for:
| • |
measurement of temperature, relative humidity, pressure etc. |
| • |
contact status from relays, thermostats etc. |
|
| Hardware outputs |
Panel Bus and LON Bus output modules available for:
| • |
control devices like servomotors (configuration of safety position is possible) |
| • |
switching devices like pumps, ventilators |
|
| Operator panels |
RS232 port available for operator panel XI582AH; this panel can be used for
adjustment of setpoints, alarm limits, fixing in/outputs, override functions
etc. |
| Management applications |
XBS or EBI PC software can be applied for a central operator and all other
building automation functions |
| Stand-alone operation |
yes |
| Bus system description |
| • |
communication bus ("physical C-bus" or "C-bus over LON") for data exchange with other EXCEL 5000 controllers and for building automation management systems (max. 30 devices per bus, incl. Centrals / Management Frontends) |
| • |
LonWorks(R) bus |
| • |
Panel bus for communication to Panel I/O modules |
|
| Transceiver type |
LonWorks(R) FTT10A |
| Mounting |
DIN rail |
| Protection class |
IP30 |
| Memory back-up |
goldcap capacitor for 72 hours buffer |
| Power supply |
24 Vacdc | 5 VA |
| Modem connection |
directly connectable |
| C-bus connection |
directly connectable |
| LonWorks(R) connection |
directly connectable |
| Panel bus connection |
directly connectable |
| Additional description |
The I/O modules need sockets for the wiring. The sockets have quick connection push in terminals. The modules are hot pluggable. Panel- and LON I/O modules can be used in any mixture per controller.
| • |
Panel I/O modules. Up to 16 modules can be used per controller. Mounting distance up to 40 m. Auto-commissioning and auto-software update is done via the controller. |
| • |
LON I/O modules. Up to 381 data points (hardware and software) can be used per controller. The mounting distance is depending on the used cable type (see LON specifications). These modules
require CARE for commissioning and software update.
|
|
| More information |
http://europe.hbc.honeywell.com/excel800 |
| Product description | Type |
| Controller | XCL8010A  |
| Product description | Type |
| 8 analog input module NTC10k, NTC20k, Ni1000, Pt1000, Pt3000, Balco, contact | XF821A | | 8 analog output module 0..10Vdc, 3-pt, binary 0/10V | XF822A | | 8 analog output module 0..10Vdc, 3-pt, binary 0/10V; with override potentiometer | XFR822A | | 12 binary input module for contact or totalizer contact 20 Hz | XF823A | | 6 relay output module SPDT 250V, 2(1) A, feedback | XF824A | | 6 relay output module SPDT 250V, 2(1) A, feedback; with override switch | XFR824A | | 3-point control output module, with override switch; for 1 actuator | XFR825A |
| Product description | Type |
| Socket for 1 analog input or output module | XS821-22 | | Socket for 1 binary input module | XS823 | | Socket for 1 relay or 3-pt output module (supplied with additional cross connector) | XS824-25 |
| Description | Additional Product Type |
| Modem cable | XW586 | | Cable for XI582 connection | XW882 | | Download cable | XW885 | | Adapter cable to use with XW882 and XW885 with XL500 controller | XW884 |
| Description | Additional Product Type |
| Manual disconnector module for analog/binary inputs and analog outputs | XS812 | | Manual disconnector module for relay outputs | XS812RO | | 10 auxiliary terminal blocks | XS814 | | 20 cross connectors for connection of 6 relay commons | XS815 | | 40 cross connectors for connection of 3 relay commons | XS817 | | 10 connector bridges | XS816 | | 10 swivel labels | XAL10 |
|